Generators

Stator Winding Earth Fault Protection of Generator

Phase to Earth Fault Protection

Phase-to-earth faults normally occur in the armature slots. The ground fault current is usually limited by the resistance in the generator’s neutral. A sensitive earth fault protection relay, as shown in the figure, is used to protect the stator winding against such faults.
The relays used in this shield (protection) scheme are;

 

earth252520fault252520relay252520in252520a252520resistance252520earthed252520generator_thumb25255b425255d-5860410
The earth fault current is usually limited by resistance (for fault current to be limited to between 200 A and 250A) or by a distribution transformer (if the fault current are to be limited to between 4A and 10A) connected in the neutral of the generator.
When the neutral is earthed through a resistor, a CT is mounted in the generator neutral and connected to a relay of type (1) and (2).
For (1), the inverse time relay requires grading with other earth fault relays in the system. For (2), no discrimination with other earth fault relays is required since the ground fault is restricted to the stator and transformer primary winding. With resistor earthing, it is impossible to protect 100% of the stator winding. The percentage of the winding protected depends on the value of the neutral earthing of the resistor and relay setting.
When there is an earth fault, the neutral current increases, and hence, the relay will operate to close the trip circuit.
However, the distributed capacitance of the stator to ground fixes a limit to the resistance value (Rn) value in the neutral.
i.e., Rn = 106 / (6πfC) ohms,
Where C is the capacitance of the stator circuit to earth/phase in μF.
If neutral is earthed through the primary winding of a transformer, earth fault protection is provided by connecting an overvoltage relay across the secondary distribution transformer. The maximum value of resistance is given by Rn = 106 / 6πfN2C ohms.

Percentage of un-protected winding (phase to Earth fault of a generator or transformer)

The value of R and x% determines the relay setting.
phase-earth252520fault252520against252520unprotected252520winding_thumb25255b325255d-8943042
The usual practice is to protect 80-85% of the alternator or transformer winding against earth fault. The remaining 15-20% from the neutral end is left unprotected. The figure for phase to earth fault shows that the setting required from differential protection is determined by the value of the neutral earthing resistor and also by the amount of stator winding to be protected.
The earth’s fault If is given by:
                           IF = (I-X)V/R
This must be equal to the primary fault setting of differential protection, Is for maximum operating current.
                          IS = (1-X)V/R and IR = V/R
                         IS = IR –XIR
                         X = (IR –IS) / IS
                             = (1-IS/IR)
           Hence % X = ( 1 – IS/IR ) x 100
IO or IS = CT primary fault setting current
IR = Earth resistor current setting (Full load current)
R = Earthing Resistance
% of Stator winding unprotected  (1-X) = (IS/IR)x100
i.e., %(1-X) = Is.R / V x 100

Jessica

Jessica, at just 27 years old, is a passionate trailblazer in the world of physics and engineering. Her insatiable curiosity about the mysteries of the universe and a knack for simplifying complex concepts have made her a rising star in the field. As a Quantum Mechanics Enthusiast, Jessica delves into the deepest realms of theoretical physics with a unique and engaging perspective. Her love for unraveling the secrets of the quantum world is infectious, making even the most perplexing ideas accessible to enthusiasts and newcomers alike.